10kva, 400v/200v single phase transformer with a resistance of 3%and reactance of 6%is supplying a current of 50A to a resistive load. The voltage across the load
Answers
Answered by
6
Given:
Transformer = 10kva
Voltage = 400v/200v
Resistance = 3%
Reactance = 6%
Current = 50A
To Find:
Voltage across the load
Solution:
For the 200V, the load current = 10000/200
= 50A
Full load percentage regulation = % Rcos Ф2 + % XsinФ2
As the load is purely resistive, the power factor will be cosФ = 1 and sinФ = 0
Thus, % regulation = %R = 3%
Output voltage across load = 200 × 97%
= 200 × 97/100
= 194
Answer: The voltage across load is 194V