3300/200V, 100KVA transformer has Nz= 80
turns. The rated secondary current 12=
Amp.
A. 30.3
B. 500
C. 50
D. 30

Answers

Answered by numls2141200
0

Answer:

It may be 50,30.3,500 or it can be 30.Now it's up to you to decide right answer

Answered by anjali1307sl
0

Answer:

The calculated value of the rated secondary current, I₂ is 500A.

Therefore, option b) 500A is correct.

Explanation:

Data given,

The voltage at the primary end, V₁ = 3300V

The voltage at the secondary end, V₂ = 200V

The given value of the rated power, P = 100KV-A = 10^{5}V-A

The turns, N_{Z} = 80turns

The rated secondary current, I₂ =?

As we know,

  • The rated power is the product of the voltage at the primary/secondary end and the current.

Therefore, we can say that:

  • The given rated power ( P ) = V₂ ( given secondary end's voltage ) × I₂ ( secondary current )

P = V_{2} \times I_{2}

I₂ = \frac{P}{V_{2} }

I₂ = \frac{10^{5} }{200} = 500A

Hence, the value of the rated secondary current, I₂, measured is 500A.