A 3 MVA, 3300/240 V, 60 Hz single-phase ideal transformer has 80 turns on the secondary winding. The values of maximum flux and full load secondary current are,
10.81 mWb, 909 A
12.42 mWb, 10 kA
13.84 mWb, 8.3 kA
11.26 mWb, 12.5 kA
None of the above
Answers
Answered by
2
Answer:
11.26 mWb, 8.3 kA
Explanation:
induced emf in the secondary winding E2 = 240V
supply voltage,f = 60Hz
number of turns of the secondary coil N2 = 80
maximum core flux = E2/4.44 f N2 = 240/4.44*60*80 = 0.0112612613 = 11.2612mWb