Math, asked by sumosinghakarjee6, 8 months ago

A hall of 30 metres by 15 metres with a ceiling height of 5 metres is to be provided with a general illumination of 120 lumens/m2. Taking a coefficient of utilisation of 0.5 and depreciation factor of 1.4 , determine the number of fluorescet tubes required, their spacing, mounting height and total wattage.Take luminous efficiency of fluorescent tube as 40 lumens per watt for 80 watt tubes. ​

Answers

Answered by knjroopa
19

Step-by-step explanation:

Given A hall of 30 metres by 15 metres with a ceiling height of 5 metres is to be provided with a general illumination of 120 lumens/m2. Taking a coefficient of utilisation of 0.5 and depreciation factor of 1.4 , determine the number of fluorescet tubes required, their spacing, mounting height and total wattage.Take luminous efficiency of fluorescent tube as 40 lumens per watt for 80 watt tubes.  

  • Given area A = 30 x 15 = 450 m^2, E = 120 lm/m^2, ƞ = 0.5, p = 1.4
  •            So φ = EA / ƞ p
  •                   = 120 x 450 / 0.5 x 1.4
  •                     = 54000 / 0.7
  •           Or φ = 77142.8 lm
  • Now flux emitted per tube will be 80 x 40 = 3200 lm
  • Therefore number of tubes required will be 77142.8 / 3200  
  •                                                                = 24

Reference link will be

https://brainly.in/question/8187817