An air conditioner of 2kW is used in an electric circuit having a fuse of 10A rating. If the potential difference of the supply is 220V, will the fuse be able to withstand, when the air conditioner is switched on? Justify your answer
Answers
Answered by
9
P=2000 W
I=10 A
V=220 V
P=VI
2000=220x10
2000≠2200
As proved by calculations, the maximum power that can be used for the A.C.
is 2200 W. Hence, the fuse would be able to withstand the power.
Answered by
6
When the air conditioner is switched on,it will not blow off.
Explanation:
The power of the air conditioner is P = 2 kW = 2000 W.
The potential difference is, V =220 V.
The rating of the fuse, I = 10 A.
The relation between power, potential difference and current is
P =V I
Substitute the values, we get
I = 9.09 A
The rating current of fuse is 10 A and calculate current slightly below, so the fuse will withstand.
Thus, when the air conditioner is switched on, it will not blow off.
#Learn More: power, potential difference and current.
brainly.in/question/8691265
Similar questions
English,
6 months ago
Science,
6 months ago
India Languages,
6 months ago
Math,
1 year ago
Math,
1 year ago
Social Sciences,
1 year ago
Physics,
1 year ago
Psychology,
1 year ago