an air conditioner of 3.2kw power rating is connected to a domestic electric circuit having a current rating of 10a .the voltage of power supply is 220v .what will happen when this air conditioner is switched on?.explain answer
Answers
Answered by
0
Answer:
ur answer
Explanation:
Given : P=3.2kW=3200W, Fuse current rating =10 A,V=220 V
We have
P=VI
3200=220×I
I=14.54 A
As the required current for the air conditioner is 14.54 A and the rated current of the fuse is 10A, so the fuse will blow cutting off the power supply.
hope it helps u
Answered by
0
Answer:
Given : P=3.2kW=3200W, Fuse current rating =10 A,V=220 V
We have
P=VI
3200=220×I
I=14.54 A
As the required current for the air conditioner is 14.54 A and the rated current of the fuse is 10A, so the fuse will blow cutting off the power supply.