An electric geyser has the ratings 2000 W,220 V marked on it. What should be the minimum rating, in whole
number of a fuse wire, that may be required for safe use with this geyser?
please answer..............
I will follow you, make you "brainliest "
Answers
Answered by
68
Answer:
Explanation:
Solution,
Here, we have
Power, P = 2000 W
Potential difference, V = 220 V
To Find,
Current, I = ?
According to the formula,
We know that
P = VI
where I is current.
P is power and,
V is potential difference.
Here, we have
P = VI
I = P/V
So, putting all the values, we get
I = P/V
⇒ I = 2000/220
⇒ I = 9.1 A.
Hence, the minimum rating in fuse is 9.14 A.
Answered by
15
Answer:
An electric geyser has the ratings 2000 W, 220 V marked on it. What should be the minimum rating, in whole number of a fuse wire, that may be required for safe use with this geyser? where I is the amount of current flowing. Hence, the minimum rating of fuse wire should be 10 A for safe use with the geyser