An electric oven of 2kW power rating is a domestic electric circuit(220.v) that has a current rating of 5A what result do you expect? Explain
Answers
Answered by
1
Answer:
Here the current drawn by the electric oven is 9.09 A, which exceeds the safe limit of the circuit that is 5A. Therefore electric fuse will melt and break the circuit.
Explanation:
PLS MARK ON BRAINLIST
Answered by
1
Answer:
Power = V×l
2kW = 220 × l
l = 2000/220
l = 9.09 A
As the amount of current flowing in the
conductor is more than 5 A, the fuse will
get broken and hence the circuit will get
open.
I hope it helps you..!!
Thank you..!!