Calculate the line current of the
3 phase 415V 50 HZ supply for the
balanced load of 3000 watt at 0.8
power factor is connected in star. |
--​

Answers

Answered by mastanshaik0429
9

Answer:

y connection, voltage applied across each impedance=4/3 so phase current = v/z=400 /10 /3 amps power

Explanation:

Hope it helps u please

Mark's as brainiest

Answered by MJ0022
0

Answer:

The line current is 5.217 amperes.

Explanation:

In a three phase balanced system of star connection, the total power consumed is P=\sqrt{3}V_LI_Lcos\alpha where cos\alpha is the power factor, V_L is the line voltage and I_L is the line current.

Between a three-phase source and load, the current through any one line is called the line current.

It is asked to find the line current of the three phase 415V, 50 HZ supply for the balanced load of 3000 watt at 0.8 power factor is connected in star.

The three phase wires are connected to a common point or star point and Neutral is taken from this common point is called as the start connection. It is also called as Y or Wye connection because of its shape.

P=\sqrt{3}V_LI_Lcos\alpha

3000=\sqrt{3} *415*I_L*0.8

I_L=\frac{3000}{\sqrt{3} *415*0.8}

I_L=5.217

Therefore, the line current is 5.217 amperes.