find the efficiency of a 150kva transformer at 25% full load at 0.8 p.f lag if the copper loss at full load is 1600W and iron loss is 1400W .ignore the effects of temperature rise and magnetising current
Answers
Answered by
7
Explanation:
0.8 pf : First, we will calculate the copper lost at full load. ... Example 2: In a 25 kVA, 2000/200 V transformer, the iron and full load ... (i) Efficiency of full load 0.8 pf lagging : % = = ... Example 3: A 40 kVa transformer has a core loss of 450 W, fullload copper loss of 850 W. If the power factor of the load is 0.8,
Answered by
4
Answer:
25 percentage of full load(KVA2)^2 =25/100×150=37.5kva
(KVA2)^2/(KVA1)^2=(Poh2)/(Poh1)
Poh2=(37.5/150)^2×1600
=100w
percentage efficiency =37.5×10^3×0.8/((37.5×10^3×0.8)+1600+100)×100
=95.23percentage