How is free ammonia removed by activated sludge process?
Answers
Answered by
1
In the paper three linear aeration controllers that can be easily implemented are presented and evaluated on the activated sludge process pilot plant. Controllers differ according to the information that is used about the process, which can be oxygen in the last aerobic reactor, ammonia in the last aerobic reactor and ammonia in the influent. The aeration controllers that are addressed are: oxygen cascade PI controller, ammonia cascade PI controller and ammonia feedforward-cascade PI controller. Experiments show that, in comparison with the oxygen cascade PI controller, the ammonia cascade PI controller allows better control of effluent ammonia and airflow savings of around 23%, while the ammonia feed forward-cascade PI controller gives the best reduction of ammonia peaks and can save up to 45% of the airflow.
sumitsainisingpdetub:
please mark my solution as brainilist
Similar questions
Math,
1 year ago