पिने योग्य जल की PH की सिमा क्या है?
Answers
भारतीय मानक ब्यूरो ने पीने लायक पानी किसे माना है। BIS 10500 : 1991 के अनुसार, पीने योग्य पानी उसे कहेंगे जिसमे निम्नलिखित बातें हो।
Sl.No Substance/Characteristic Requirement Permissible Limit(Desirable Limit)in absence of Alternate source
Essential characteristics
1Colour, ( Hazen units, Max )525
2OdourUnobjectonableUnobjectionable
3TasteAgreeableAgreeable
4Turbidity ( NTU, Max)510
5pH Value6.5 to 8.5No Relaxsation
6Total Hardness (as CaCo3) mg/lit.,Max300600
7Iron (as Fe) mg/lit,Max0.31
8Chlorides (as Cl) mg/lit,Max.2501000
9Residual,free chlorine,mg/lit,Min0.2--
Desirable Characteristics
10Dissolved solids mg/lit,Max5002000
11Calcium (as Ca) mg/lit,Max75200
12Copper (as Cu) mg/lit,Max0.051.5
13Manganese (as Mn)mg/lit,Max0.10.3
14Sulfate (as SO4) mg/lit,Max200400
15Nitrate (as NO3) mg/lit,Max45100
16Fluoride (as F) mg/lit,Max1.91.5
17Phenolic Compounds (as C 6 H5OH)0.0010.002mg/lit, Max.
18Mercury (as Hg)mg/lit,Max0.001No relaxation
19Cadmiun (as Cd)mg/lit,Max0.01No relaxation
20Selenium (as Se)mg/lit,Max0.01No relaxation
21Arsenic (as As) mg/lit,Max0.05No relaxation
22Cyanide (as CN) mg/lit,Max0.05No relaxation
23Lead (as Pb) mg/lit,Max0.05No relaxation
24Zinc (as Zn) mg/lit,Max515
25Anionic detergents (as MBAS) mg/lit,Max0.21
26Chromium (as Cr6+) mg/lit,Max0.05No relaxation
27Polynuclear aromatic hydro carbons----
(as PAH) g/lit,Max
28Mineral Oil mg/lit,Max0.010.03
29Pesticides mg/l, MaxAbsent0.001
30Radioactive Materials
IT WILL DEFINITELY HELP U....