Physics, asked by mahaleprashant21075, 1 month ago

the coefficient of performance of a room air conditioner is 3.if the rate of doing work is 2kW,find the heat current​

Answers

Answered by sonuvuce
10

The heat is current is 4 kJ/s

Explanation:

Given:

COP of a room conditioner is 3

Rate of doing work is 2kW = 2kJ/s

To find out:

The heat current

Solution:

We know that

(COP)_R=\frac{Q_L}{W}

Here,

(COP)_R=3

W=2 kW

\therefore 2=\frac{Q_L}{2}

\implies Q_L=2\times 2=4 kJ/s

Hope this answer is helpful.

Know More:

Q: A refrigerator whose coefficient of performance is 5 extracts heat from the cooling compartment at the rate of 250 j/cycle. How much electric energy is spent per cycle? How much heat per cycle is discharged to the room?

Click Here: https://brainly.in/question/8338212

Answered by sanikashedge52
1

Answer:

6kW

Explanation:

K=3

p=2kW

  • Heat (H)=KP=3×2=6kW