Science, asked by rohitchavan3196, 5 months ago

The rating required for a DG set with 500 kW
connected load and with diversity factor of 1.5,
80% loading and 0.8 power factor is .........
(a) 520 kVA
(b) 600 KVA
(c) 625 kVA
(d) 500 KVA​

Answers

Answered by blackbulls
6

Answer:

Explanation:

a) 520 kVA

Answered by sarahssynergy
1

The rating required for a DG set is 625.

Explanation:

  • Total Connected Load is the mechanical and electrical load (in kW) that will be connected (or to consumed) for that particular area.
  • Loading indicate amount of current flowing in it when it gets loaded.  
  • Approximately kVA = kW / power factor = 500/ 0.8   = 625 kVA.