Two devices of rating 44W,200 V and 11W,220 V are connected in series. the combination is connected across a 440W mains. the fuse of which of the two devices is likely to burn when the switch is ON.? justify your answer
Answers
229.95 V across the device of 11 W, 220 V ratting is sufficient to burn the fuse of device
Explanation:
given data
devices 1 power = 44 W
voltage = 200 V
devices 2 power = 11 W
voltage = 220 V
solution
we know that here Resistance that is express as
Resistance R = ......................1
put here value for both device
device 1 Resistance R =
device 1 Resistance R = 909.09
device 2 Resistance R =
device 2 Resistance R = 1100
connected in series
so current will be
current I =
current I = \frac{220+200}{1100+909.09}
current I = 0.209
so
voltage across device 1 = I × R
voltage across device 1 = 0.209 × 909.09 = 189.99
voltage across device 2 = I × R
voltage across device 2 = 0.209 × 1100 = 229.95
so here 229.95 V across the device of 11 W, 220 V ratting is sufficient to burn the fuse of device