A carnot heat pump is used to heat a house. the outside temperature is -3°c and the indoor temperature is 27°c. if the heat loss from the house is 40kw, the power required to operate the heat pump is

Answers

Answered by Ursus
0

The power required to operate the heat pump is 4.44 kW

The COP of Carnot heat pump is given as

n=T_high/(T_high-T_low )=(heat supplied)/(Heat supplied-heat loss)

Plugging the values in the above equation

300/(300-270)=Q/(Q-40)

Q=44.44 kW

Now the power required to operate the heat pump

Power=Heat supplied-Heat loss

P=44.44-40=4.44 kW

Therefore the power required is 4.44 kW