A single-phase transformer has a turns-ratio of 144/432 and
operates at a maximum flux of 7.5 mWb at 50 Hz. When
working on no load, it takes 0.24 kVA at a power factor of 0.26
lagging from the supply. If it supplies a load of 1.2 kVA at a
power factor of 0.8 lagging, determine (a) the magnetizing
current, (b) the primary current, and (c) the primary power
factor.
Answers
Given that,
Turns ratio = 144/432
Maximum flux = 7.5 mWb
Frequency = 50 Hz
We need to calculate the primary voltage
Using formula of voltage
Put the value into the formula
We need to calculate the secondary voltage
Using formula of voltage
Put the value into the formula
At no load,
We need to calculate the value of
Using formula of factor
Put the value into the formula
We need to calculate the current
Using formula of power
Put the value into the formula
(I). We need to calculate the magnetizing current
Using formula of magnetizing
Put the value into the formula
Now, no load current is
At load,
We need to calculate the value of
Using formula of factor
Put the value into the formula
We need to calculate the secondary current
Using formula of power
Put the value into the formula
Now, load current is
(II). We need to calculate the primary current
Using formula of primary current
Put the value into the formula
We need to calculate the total current
Using formula of total current
Put the value into the formula
(III). We need calculate the power factor
Using formula power factor
Hence, (I). The magnetizing current is 0.9667 A.
(II). The primary current is
(III). The primary power factor is 0.7319.