An electrician puts a fuse of rating 5 A in that part of domestic electrical circuit in which an electrical heater of rating 1.5kW , 220V is operating .What is likely to happen in this case and why? What change if any needs to be made?

Answers

Answered by biligiri
6

Answer:

the current drawn by 1.5 kw heater at 220 volts will be (1.5/1000)/220 = 6.8 Amp.

5A fuse will blow off on switching on the power.

Electrician needs to replace the fuse with 10 A fuse.

Answered by palsabita1957
17

Answer:

The above amount of current is greater than the rated value of fuse current. Hence, the fuse will melt and break the circuit.

Please refer to the above attachment.